MPB/HT GALV

3D Presentation Zoom

Designations

MPB 1 200HT GALV
 

  1. Model fan
The MPB-HT fans are designed for transporting highly polluted air at maximum temperature up to 250°C. They may be used as exhaust fans in boilers or for mixing gases.
 

Application

The MPB-HT fans are designed for transporting highly polluted air at maximum temperature up to 250°C. They may be used as exhaust fans in boilers or for mixing gases.

Construction

Medium-pressure, radial directly-driven fans. The welded rotors, provided with straight blades of steel sheet are dynamically balanced according to ISO1940.

The housing is made of welded, zinc-plated steel sheet. The shaft of the motor is provided with dispersing disks to protect it against high temperature.

As a standard, the fans are supplied in the RD 270 configuration. Fans in other configurations are available on request.

Electric motor

Asynchronous, three phase 230/400V or 50Hz. The motors are made in accordance with IEC 60072 and IEC 60034 standards, and have been awarded with a CE mark. Insulation class F, degree of protection IP55.

On request, we can deliver motors driven by another voltage or frequency, adapted for voltage control or for a frequency converter, provided with an independent cooling system and/or with sensors (either bimetallic or posistor).
Name Nominal
voltage [V]
Speed
[r.p.m.]
P max
[W]
I max
[A]
Q max
[m3/h]
P
static [Pa]
Weight
[kg]
GMT-HT-100-075T 400 2850 750 1.65 1290 1925 35.5
GMT-HT-130-110T 400 2890 1100 2.5 1610 2110 38.5
GMT-HT-200-150T 400 2880 1500 3 1900 2075 51.8
GMT-HT-300-300T 400 2870 3000 6.3 2900 2300 60