MSB

3D Presentation Zoom

Designations

MSB- 1 2- 2 400/125- 3 4004 T
 

  1. Number of motor poles (rotation speed)
  2. Model
  3. Power
    400 - 400 x 10 = 4 000W
  4. Electric motor
    T Three-phase motor
Transport of dust-containing air
 

Application

Transport of dust-containing air.

Construction

Medium-pressure centrifugal fans with direct drive.

Impellers with straight blades, backward curved, welded from aluminum sheet, dynamically balanced as per ISO 1940-1 standard. Housing welded from steel sheet.

As a standard, the fans are manufactured in LG270 configuration (MSB-2-560/180-3000 and MSB-2-560/180-3700 fans are manufactured as a standard in RD270 configuration).

Electric motor

Electric motor made in accordance with applicable directives and efficiency classes, CE marked. Insulation class - F. Degree of protection - IP55.

Power supply - AC 230 / 400V 50Hz, 400V 50Hz or 400 / 690V 50Hz (depending on motor power).

Fans with motors in different designs: see Table of Special Designs.
Name Pole Nominal
voltage [V]
Speed
[r.p.m.]
P max
[W]
I max
[A]
Q max
[m3/h]
P
static [Pa]
Weight
[kg]
Temp.
min.
[oC]
Temp.
max.
[oC]
MSB-2-315/102-110T LG270 IE3 400 2900 1100 2.7 4500 1400 40 -20 60
MSB-2-355/125-220T IE3 400 2900 2200 4.6 5500 1650 45 -20 60
MSB-2-400/125-400T LG270 IE3 400 2900 4000 7.9 8000 2300 55 -20 60
MSB-2-450/125-750T IE3 400 2900 7500 14 10000 3400 88 -20 60
MSB-2-500/100-1100T IE3 400 2900 11000 21.2 17500 3600 125 -20 60
MSB-2-560/80-1500T IE3 400 2900 15000 26.2 19000 4400 140 -20 60