VASP

3D Presentation Zoom

Designations

VASP / 1 2- 2 12- 3 0374 T
 

  1. Number of motor poles (rotation speed)
  2. Size of fan housing
  3. Power 037 x 10 = 0,37 kW
  4. S Single-phase motor
    T Three-phase motor
The VASP fans are designed for transporting media that contain aggressive chemical compounds, (acidic or basic fumes), or for exhausting dusted air, smoke, combustion gases, etc.
 

Application

The VASP fans are designed for transporting media that contain aggressive chemical compounds, (acidic or basic fumes), or for exhausting dusted air, smoke, combustion gases, etc. They are suitable for use in exhaust installations, laboratory hoods, and in chemical plants.

Construction

Medium-pressure, radial directly-driven fans. Housing, the rotor, the plate of the motor and the air inlet are made of polypropylene reinforced by UV irradiation. The housing is a compact structure. Rotors provided with forward-tilted blades are dynamically balanced according to ISO 1940. The plate of the motor is assembled to the base with a stainless screws; additional rubber gasket between the plate and the housing provides tightness of the housing. As a standard, the motor is affixed to a base made of stell sheet painted with powder paint (grey (RAL 7042) for models 12, 14 and 16 or black (RAL 9005) for the model 10) a support made of stainless steel available on request. Fans without a support are also available.

As a standard, the fans are supplied in the LG90 configuration. Fans in other configurations are available on request (only LG configurations are available). The fan is manufactured according to AMCA 210-85 and ISO 5801. The fans have been awarded with a CE mark. Maximum temperature of the transported medium is 40°C. Temperature of air surrounding the motor -15°C to 40°C Any non-standard and special orders require a prior contact with Venture Industries Sp. z o.o.

Electric motor

Asynchronous, three-phase 230/400V or 400V, 50Hz, or single-phase 230V, 50Hz, with a capacitor.
The motors are manufactured in accordance with IEC 60072 and IEC 60034 standards, and have been awarded with a CE mark. Insulation class F degree of protection IP 55. On request, we can deliver motors driven by another voltage or frequency, with an increased degree of protection, adapted for voltage control or for a frequency converter, provided with an independent cooling system and/or with sensors (either bimetallic or posistor).
Name Nominal
voltage [V]
Speed
[r.p.m.]
P max
[W]
I max
[A]
Q max
[m3/h]
P
static [Pa]
Weight
[kg]
Temp.
min.
[oC]
Temp.
max.
[oC]
VASP/4-10-006S 230 1500 60 0.9 90 110 2.7 -20 40
VASP/4-12-025S 230 1500 250 2.5 270 220 7.8 -20 40
VASP/2-10-012S 230 3000 120 1.3 180 420 4.4 -20 40
VASP/2-12-037S 230 3000 370 3 530 830 5.6 -20 40
VASP/2-14-110S 230 3000 1100 6.4 1080 1350 12.8 -20 40
VASP/4-10-006T 400 1500 60 0.63 110 110 3.5 -20 40
VASP/4-12-025T 400 1500 250 1.7 270 220 8.6 -20 40
VASP/2-10-012T 400 3000 120 0.8 210 420 5.3 -20 40
VASP/2-12-037T 400 3000 370 1.68 530 830 7.4 -20 40
VASP/2-14-110T 400 3000 1100 4.7 1080 1350 15.7 -20 40
VASP/2-16-220T 400 3000 2200 8.8 1850 2000 22.6 -20 40

Performance curves