JET Ex

Specially designed, chemically resistant JET fans, provided with the ATEX mark, comply with the requirements of the ATEX Directive, concerning devices that may be used in potentially explosive atmospheres.
 

Explosion-proof radial JET fans

Chemically resistant JET fans, provided with the ATEX mark, comply with requirements of the ATEX Directive, concerning devices that may be used in potentially explosive environments.

Designed for use in potentially explosive environments, other than coal mines and dog headings. 

They meet requirements set for group II category 3G – zone 2 (Z2). The explosion-proof JET fans that comply with Ex II 3Gc IIB T4 ATEX are available in standard sizes but only with three-phase motors. 

JET EX motors are not provided with speed control.
Installation shall comply with applicable regulations and provisions specified in the operation and maintenance manual.
Name Nominal
voltage [V]
Speed
[r.p.m.]
P max
[W]
I max
[A]
Q max
[m3/h]
P
static [Pa]
Weight
[kg]
Temp.
min.
[oC]
Temp.
max.
[oC]
JET 20 EXII 3Gc IIBT4 ATEX 0.18kW 400 950 180 0.65 600 80 25 -15 60
JET 20 EXII 3Gc IIBT4 ATEX 0.75kW 400 2800 750 1.8 1800 800 28 -15 60
JET 25 EXII 3Gc IIBT4 ATEX 0.18kW 400 950 180 0.65 1400 150 28 -15 60
JET 25 EXII 3Gc IIBT4 ATEX 0.37kW 400 1400 370 1.2 1900 400 28 -15 60
JET 25 EXII 3Gc IIBT4 ATEX 2.2kW 400 2800 2200 5.5 2200 1500 32 -15 60
JET 30 EXII 3Gc IIBT4 ATEX 1.1kW 400 1400 1100 3.7 3400 580 48 -15 60

Performance curves