MPB-R

3D Presentation Zoom
MPB-R roof fans have many applications in contaminated air extraction systems and in pneumatic transport. Typical applications: local exhaust, contaminated air exhaust, vehicle exhaust extraction systems.
 

Application

MPB-R roof fans have numerous applications in dusty air extract systems and pneumatic transport systems.

Typical applications:
  • Local exhaust systems
  • Dusty air extract systems
  • Vehicle fumes extraction systems

Construction

Medium-pressure centrifugal fan with direct drive. Impellers with straight blades cast from aluminum alloys; impeller dynamically balanced as per ISO1940 / 1 standard, housing welded from steel sheet. Fans matted with grey RAL7042.

Impellers welded from stainless/acid-resistant steel, copper alloys; housing made of stainless and galvanized steel sheet can also be supplied on request. Maximum pumped medium temperature of 80°C.

Non-standard or special designs require prior contact with Venture Industries Sp. zoo.

Electric motor

Electric motor made in accordance with applicable directives and efficiency classes, CE marked. Insulation class - F. Degree of protection - IP55. Power supply - AC 230 / 400V 50Hz, 50Hz 400V, 400 / 690V 50Hz or 230V single-phase 50Hz (depending on fan model and motor power). Fans with motors in different designs; see Table of Special Designs.
Name Nominal
voltage [V]
Speed
[r.p.m.]
P max
[W]
I max
[A]
Q max
[m3/h]
P
static [Pa]
Weight
[kg]
Temp.
min.
[oC]
Temp.
max.
[oC]
GMT-R-60-037S 230 2760 370 3 580 1360 18.2 -15 40
GMT-R-60-037T 400 2800 370 1 580 1360 16.9 -30 60
GMT-R-80-037S 230 2760 370 3 810 1235 21.9 -15 40
GMT-R-80-037T 400 2800 370 1 810 1235 20.6 -30 60
GMT-R-80-055S 230 2780 550 3.6 1200 1235 22.9 -15 40
GMT-R-80-055T 400 2790 550 1.35 1200 1235 21.8 -30 60
GMT-R-100-055S 230 2780 550 3.6 690 1800 24 -15 40
GMT-R-100-055T 400 2790 550 1.35 690 1800 22.9 -30 60
GMT-R-100-075S 230 2800 750 5 1150 1800 26.3 -15 40
GMT-R-100-075T 400 2890 750 1.9 1150 1800 27.2 -30 60
GMT-R-130-075S 230 2800 750 5 1230 2000 27.3 -15 40
GMT-R-130-075T 400 2890 750 1.9 1230 2000 28.2 -30 60
GMT-R-130-110S 230 2780 1100 7.2 1635 2000 27.4 -15 40
GMT-R-130-110T 400 2890 1100 2.5 1635 2000 29.5 -30 60
GMT-R-200-110S 230 2780 1100 7.2 1990 1940 30.4 -15 40
GMT-R-200-110T 400 2890 1100 2.5 1990 1940 32.5 -30 60
GMT-R-250-150T 400 2880 1500 3 1760 2300 41.6 -20 40
GMT-R-300-220T 400 2895 2200 4.6 2030 2070 42.4 -20 40
GMT-R-400-300T 400 2870 3000 6.3 3260 2200 48.5 -20 40
GMT-R-500-400T 400 2895 4000 7.2 5050 2170 75.9 -20 40

Performance curves